P&QR Power & Quality Recorder

P&QR Power & Quality Recorder

Application

  • Power quality monitor–measures voltage and frequency profiles, voltage dips and surges, loss or supply, harmonic content, flicker, voltage and current imbalance
  • Transient fault recorder–analog inputs are sampled at up to 128 samples per cycle with a maximum record length of 2 seconds
  • Disturbance Recorder/Logger–analog inputs are sampled at up to 2 samples per cycle with RMS measurements recorded up to one minute
  • Trend Recording–input and computed quantities are logged as maximum, minimum and average quantities every minute for up to 16 weeks.
  • Remote Capabilities-via Ethernet or modem, and the process can be automated using the record’s Auto-Call or Auto-Poll features.
  • Software–wide range of application software for communicating, configuring, downloading, displaying and analyzing recorded data. Auto-poll/Call automates the complete process of retrieving your recorded data.

Specifications

INPUTS
Number of channels

  • 8 (4 voltage, 4 current) consult factory for other configurations Voltage Inputs
  • 150/300/600 RMS maximum, Star (wye) or delta connections Current Inputs
  • 1/5/100/200/500/1000 A RMS nominal thru external CTs. designed to record to 40% over-range
    Frequency Response
  • 40Hz-3kHz. (+0dB, -3dB for voltages) DC-3kHz (+0dB for currents) Accuracy
  • Better than 0.2% of full scale

REAL TIME CLOCK
Clock Source

  • 32,768 Hz internal crystal oscillator

Resolution

  • 1 ms

Range

  • Time and date (including leap year and day of the year) Synchronization
  • 50/60 Hz from voltage input

ENCLOSURE
Mounting

  • Wall (internal terminals) — 11.75 in. x 16.0 in. x 8.25 in. (300 mm x 400 mm x 210 mm)
  • 19″ Rack Mounting — 13.25 in. x 19.0 in. x 5.25 in. (336 mm x 482 mm x 133 mm)
  • Portable — 14.25 in. x 13.75 in. x 5.25 in. (362 mm x 349 mm x 133 mm) Weight
  • 13.2-17.6 lbs. (6-8 kg) depending on enclosure style

CERTIFICATION
CE

Description

Features

  • Channel input: 4 voltage 4 current
  • 14 bit recording
  • 8 Mbytes internal memory; 6.4 GB hard disk
  • Measures waveform faults, voltage dips and surges, harmonics, flicker and imbalance
  • Communications via RS232 serial port and optional Internal modem and Ethernet
  • Powerful P&Qs software for communications and analysis

Related Market

  • Power generation

Title

Go to Top